-
Backflow Type:
Dual Check
-
Color/Finish:
Brass
-
End Style:
FNPT
-
IsInactive:
false
-
Pressure Rating:
175 PSI (Inlet Pressure), 15 PSI (Outlet Pressure)
Automatic Filling Back Flow Preventer Valve; Type Pre-Adjustable; Nominal Size 1/2 Inch; End Connection Soldered Union x Female Threaded; End to End Distance 8-5/8 Inch; Body Material Brass; Seat Material NBR; Temperature Rating 150 Deg F; Pressure Rating 175 PSI (Inlet Pressure), 15 PSI (Outlet Pressure); Inclusions/Features PA 66 GF 30 Cover, Sliding Surfaces in Anti-Scale Plastic, Diaphragm and Seals in NBR and Removable Cartridge; Applicable Standard ASSE 1012, CSA B64.3; Setting Pressure Range 3 to 60 PSI; Pressure Gauge Scale 0 to 60 PSI; Suitable Fluids WaterThe automatic filling valve is a device consisting of a pressure reducing valve with compensating seat, visual system pressure setting indicator, an inlet filter, anti-scale internal parts, a shut-off valve (round knob on bottom) and a check valve. It is installed on the water inlet piping in sealed heating systems, and its main function is to maintain the pressure of the system at a set value, automatically filling up with water as required. The valve is pre-adjustable, meaning it can be set to the desired pressure value before the system charging phase. After installation, during the filling or topping-off phase, the water feed will stop when the set pressure is reached. This valve fills 50% faster than other valves. There are no levers to flip or valve to close. Pre-assembled with the 573 series backflow preventer, the AutoFillâ„¢ Combo features an atmospheric vent which is designed to protect drinking water systems from return flow, caused by back-siphoning or back pressure, of contaminated fluids.