Configuring or reconfiguring the Variable Frequency Drive at start-up is necessary because a factory setting may be incorrect or there may be an update needed. A new VFD comes with only basic HVAC configuration, and the blower won’t run until it’s configured properly.
First, you will need to purchase an ABB Remote keypad kit, CRDISKIT001A00.Factory installed VFDs do not come with keypad display, while replacement VFDs come with keypad installed. It is required to finish configuring the replacement VFD.
VFD start-up instructions can be found on HVAC Partners, on form IIVFD-07, and the instruction manual is included in CRDISKIT001A00. You can find the appendix chart on pages 34-39, and then locate the unit you are working on.
This video features a Bryant rooftop unit, part number 580JP16D350A2A0AD (located on page 35), and we’ll walk through the steps needed. For a different part number, the values may differ but the steps will be the same. This information will be listed on the blower door on newer RTUs.
Steps to configuring your VFD:
Install the keypad. (2:13 mark of the video)
Installed on the front of the new drive
A cat5 extension cable can be used so keypad can be held in your hand (CRDISKIT001A00 includes a cat5 cable)
Install keypad
Push the Off button on the key pad before configuration
Locate Bryant motor and drive number (not manufacturer part number) on the chart. (3:12 mark)
Motor HD58FE654
VFD HK30WA352
Find unit parameters on the chart.
Match motor HP and voltage if exact number isn’t found
DO NOT USE START-UP ASSISTENCE - PRESS NO WHEN ASKED TO USE IT!!
On the keypad push the Menu button, and select Parameters. (5:00 mark)
Press Enter
Scroll to first parameter in this example, setting 99, then press select
Scroll to the first parameter, 9905: (5:35 mark)
Press edit
Set your voltage, in this case 230, and press save
Scroll to next parameter, 9906:
Press edit
Set your nominal amps, in this case 9.2, and press save
Complete 99 parameters in the same way:
Press exit
Scroll to next parameter, 12: (7:13 mark)
Press select
Scroll to 1201:
Press Edit
Set Constant speed setting 1201 to DI 2,3
Press save
Complete 12 parameters.
Continue across the chart until all parameters have been set.
Press Exit
Press Auto before removing key pad
If Start-up assistant has been used, you’ll need to reset to your defaults. (13:05 mark)
Change Parameter 9902 from HVAC Default to any Macro